This free UPS runtime calculator estimates how long an uninterruptible power supply will keep your computer, gaming PC, NAS, server, router or modem running during a power outage. Enter the load in watts and the UPS battery's voltage and amp-hours — printed on the battery or in the manual — to get the runtime, and see what size UPS in VA and watts you need. It accounts for inverter losses, battery age and the Peukert effect that shortens runtime at high loads.
How UPS runtime is calculated
Battery current (A) = load W ÷ (battery V × inverter efficiency)
Runtime (h) = 20 × (Ah × health ÷ (current × 20))k
Recommended UPS = load × 1.25 W (≈ that ÷ 0.6 in VA)
The second line is Peukert's law for a battery rated at its 20-hour rate. The exponent k is about 1.2 for the sealed lead-acid batteries in most UPS units and close to 1.05 for lithium. It is why doubling the load more than halves the runtime of a lead-acid UPS.
Worked example
A 1500 VA UPS has two 12 V 9 Ah batteries in series (24 V). With a 150 W load and 85% efficiency, the batteries supply 150 ÷ (24 × 0.85) = 7.4 A. Runtime = 20 × (9 ÷ (7.4 × 20))1.2 ≈ 42 min.
UPS runtime chart
Estimated runtime of typical UPS sizes with new sealed lead-acid batteries. Loads above what each size can supply are left blank.
| UPS (battery) | 20 W | 50 W | 100 W | 200 W | 300 W | 500 W |
|---|---|---|---|---|---|---|
| 600 VA (12 V 7 Ah) | 2 h 32 min | 51 min | 22 min | 10 min | 6 min | — |
| 1000 VA (12 V 9 Ah) | 3 h 25 min | 1 h 8 min | 30 min | 13 min | 8 min | 4 min |
| 1500 VA (24 V, 2 × 9 Ah) | 7 h 51 min | 2 h 37 min | 1 h 8 min | 30 min | 18 min | 10 min |
| 3000 VA (48 V, 4 × 9 Ah) | 18 h 3 min | 6 h 1 min | 2 h 37 min | 1 h 8 min | 42 min | 23 min |
Battery layouts vary between models; check your UPS manual for the battery voltage and amp-hour rating. Manufacturer runtime charts are the best reference for a specific model.
Typical power use of devices on a UPS
| Device | Typical watts |
|---|---|
| Wi-Fi router + modem | 15–25 W |
| NAS (2–4 drives) | 20–50 W |
| Laptop (charging) | 30–90 W |
| Office PC + monitor | 80–150 W |
| Gaming PC + monitor (under load) | 300–600 W |
| Small home server | 50–150 W |
Related calculations
- Need hours of backup rather than minutes? See how long a power station lasts with the battery runtime calculator.
- For long outages, size a generator with the generator size calculator.
- Find what an always-on PC or server costs per year with the electricity cost calculator.